Part Number Hot Search : 
LSI20 PLL40 NTE399 70475 0KGKT 128J3 ZMM4V3 74HC740
Product Description
Full Text Search
 

To Download PDRP-1002 Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
  the PDRP-1002/PDRP-1002e agent release control system manual system sensor 3825 ohio avenue st. charles, il 60174 1-800-sensor2 fax: 630-377-6495 pdrp1002.cd document 51135 03/11/99 revision: a pn 51135:a ecn 99-017 i56-1358-00
2 the PDRP-1002 pn 51135:a 03/11/99 installation precautions ? adherence to the following will aid in problem-free installation with long-term reliability: warning - several different sources of power can be connected to the fire alarm control panel. disconnect all sources of power before servicing. control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. do not attempt to install, service, or operate this unit until this manual is read and understood. caution - system reacceptance test after software changes: to ensure proper system operation, this product must be tested in accordance with nfpa 72-1993 chapter 7 after any programming operation or change in site-specific software. reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. all components, circuits, system operations or software functions known to be affected by a change must be 100% tested. in addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices must also be tested and proper system operation verified. this system meets nfpa requirements for operation at 0-49 o c/ 32-120 o f and at a relative humidity of 85% rh (non-condensing) at 30 o c/86 o f. however, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. therefore, it is recommended that this system and its peripherals be installed in an environment with a nominal room temperature of 15-27 o c/60-80 o f. verify that wire sizes are adequate for all initiating device loops. most devices cannot tolerate more than a 10% i.r. drop from the specified device voltage. like all solid state electronic devices , this system may operate erratically or can be damaged when subjected to lightning induced transients. although no system is completely immune from lightnin g transients and interferences, proper grounding will reduce susceptibility. overhead or outside aerial wiring is not recommende d due to an increased susceptibility to nearby lightning strikes. cons u with the technical services department if any problems are anticipated or encountered. disconnect ac power and batteries prior to removing or inserting circuit boards. failure to do so can damage circuits. remove all electronic assemblies prior to any drilling, filing, reami n or punching of the enclosure. when possible, make all cable entrie s from the sides or rear. before making modifications, verify that they will not interfere with battery, transformer and printed circuit board location. do not tighten screw terminals more than 9 in-lbs. over tightenin may damage threads, resulting in reduced terminal contact pressur e and difficulty with screw terminal removal. this system contains static-sensitive components always ground yourself with a proper wrist strap before handling any circuits so tha t static charges are removed from the body. use static suppressive packaging to protect electronic assemblies removed from the unit. follow the instructions in the installation, operating and programming manuals. these instructions must be followed to avoi d damage to the control panel and associated equipment. facp operation and reliability depend upon proper installation. fire alarm system limitations an automatic fire alarm system - typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices and a fire alarm control with remote notification capability can provide early warning of a developing fire. such a system, however, does not assure protection against property damage or loss of life resulting from a fire. any fire alarm system may fail for a variety of reasons: smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in walls, or roofs, or on the other side of closed doors. smoke detectors also may not sense a fire on another level or floor of a building. a second floor detector, for example, may not sense a first floor or basement fire. furthermore, all types of smoke detectors - both ionization and photoelectric types, have sensing limitations. no type of smoke detector can sense every kind of fire caused by carelessness and safety hazards like smoking in bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with matches, or arson. important! smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling and /or power. if detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire. audible warning devices such as bells may not alert people if the s devices are located on the other side of closed or partly open doors o are located on another floor of a building. a fire alarm system will not operate without any electrical power. i ac power fails, the system will operate from standby batteries only f o a specified time. rate-of-rise heat detectors may be subject to reduced sensitivity over time. for this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. equipment used in the system may not be technically compatible with the control panel. it is essential to use only equipment listed fo service with your control panel. t elephone lines needed to transmit alarm signals from a premise to central monitoring station may be out of service or temporarily disabled. the most common cause of fire alarm malfunctions, however, is inadequate maintenance. all devices and system wiring should be tested and maintained by professional fire alarm installers following written procedures supplied with each device. system inspection a n testing should be scheduled monthly or as required by national and/ o local fire codes. adequate written records of all inspections should b kept. fcc warning warning: this equipment generates, uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications, it has been tested and found to comply with the limits for class a computing device pursuant to subpart b of 15 of fcc rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense. canadian requirements this digital apparatus does not exceed the class a limits for radiati o noise emissions from digital apparatus set out in the radio interference regulations of the canadian department of communications. le present appareil numerique n'emet pas de bruits radioelectrique s depassant les limites applicables aux appareils numeriques de la classe a prescrites dans le reglement sur le brouillage radioelectrique edicte par le ministere des communications du canada. while installing a fire alarm system may make lower insurance rates possible, it is not a substitute for fire insurance!
the PDRP-1002 pn 51135:a 03/11/99 3
4 the PDRP-1002 pn 51135:a 03/11/99
the PDRP-1002 pn 51135:a 03/11/99 5 nfpa standards this control panel complies with the following nfpa standards: nfpa 12 co 2 extinguishing systems (high pressure only) nfpa 12a halon 1301 extinguishing systems nfpa 12b halon 1211 extinguishing systems nfpa 72 central station signaling systems (automatic, manual, and waterflow). protected premises unit (requires noti?fire 911ac dact or ms-5012 slave communicator)* nfpa 72 local (automatic, manual, waterflow and sprinkler supervisory) fire alarm systems nfpa 72 auxiliary (automatic, manual, and waterflow) fire alarm systems. (requires 4xtm) nfpa 72 remote station (automatic, manual, and waterflow) fire alarm systems. requires 4xtm, notifire 911ac dact* nfpa 2001 clean agent fire extinguishing systems *applications which require the noti?fire 911ac are not fm approved. additional information before proceeding, the installer should be familiar with the following documents and standards: nfpa standards: nfpa 12 co 2 fire extinguishing systems nfpa 12a halon 1301 fire extinguishing systems nfpa 12b halon 1211 fire extinguishing systems nfpa 72 installation, maintenance and use of central station signaling systems nfpa 72 local, auxiliary, remote station and proprietary fire alarm systems nfpa 72 automatic fire detectors nfpa 72 installation, maintenance and use of notification appliances for fire alarm systems nfpa 72 testing procedures for signaling systems nfpa 2001 clean agent fire extinguishing systems underwriters laboratories documents: ul 38 manual actuated signaling boxes ul 217 smoke detectors, single and multiple station ul 228 door closers - holders for fire alarm systems ul 268 smoke detectors for fire alarm systems ul 268a smoke detectors for duct applications ul 346 waterflow indicators for fire alarm systems ul 464 audible signaling appliances ul 521 heat detectors for fire alarm systems ul 864 standard for control units for fire alarm systems ul 1481 power supplies for fire alarm systems ul 1638 visual signaling appliances ul 1971 signaling devices for the hearing impaired can/ulc-s524-m91 standard for installation of fire alarm systems can/ulc-s527-m87 standard for control units for fire alarm systems other: nec article 300 wiring methods nec article 760 fire alarm systems applicable local and state building codes requirements of the local authority having jurisdiction notifier device compatibility document, 15378 ada americans with disabilities act
1 the PDRP-1002/PDRP-1002e input circuits 6 the PDRP-1002 pn 51135:a 03/11/99 1 the PDRP-1002/PDRP-1002e features  microprocessor-controlled  power-limited on all circuits except municipal box output  alarm and trouble resound  four class a (style d)/class b (style b) initiating device circuits  two class a (style z)/class b (style y) notification appliance circuits  two class b (style y) release circuits  general alarm and trouble relays  optional module for 4 zone/function relays (4xzm)  optional transmitter module (4xtm). complies with nfpa 72 auxiliary and remote station fire alarm systems  optional volt/amp meter module (4xmm)  optional supervised remote annunciator (rza-4x)  requires led interface module (4xlm)  optional digital communicator (notifire 911ac)*  complies with nfpa 72 central station and remote station fire alarm systems  supervisory input option  delay timer (adjustable)  three abort function options  designed for suppression standards nfpa 12, 12a and 12b  disable/enable controls per initiating zone  last event recall  battery/earth fault supervision  fuse protection on all notification/release circuits  rms regulated output power, 2.25 amps  7 amp/hour to 15 amp/hour battery options, up to 90 hours standby  resettable and non-resettable regulated power outputs  extensive transient protection  watchdog timer to supervise microprocessor  output circuits protected against false activations  slide-in zone identification labels  steel cabinet 14.5 in (368.3 mm) wide by 16 in ( 406.4 mm) high by 5 in (127 mm) deep  dead-front dress panel option (dp-4x)  trim ring for flush mount between 16 in (406.4 mm) center studs (tr-4xr)  abort and manual release circuits  cross-zone option * applications which require the notifire 911ac are not fm approved . circuits input circuits detector zone 1, class a (style d)/class b (style b) detector zone 2, class a (style d)/class b (style b) abort, class a (style d)/class b (style b) manual release, class a (style d)/class b (style b) output circuits (optional auxiliary relays track these four circuits) notification appliance circuit 1, class a(style z)/class b (style y) notification appliance circuit 2, class a(style z)/class b (style y) releasing circuit 1, class b (style y) releasing circuit 2, class b (style y)/supervisory input, class b (style b)
front panel control switches 1 the PDRP-1002/PDRP-1002e the PDRP-1002 pn 51135:a 03/11/99 7 front panel control switches switch 1 tone silence switch 2 alarm silence switch 3 alarm activate switch 4 system reset figure 1 PDRP-1002/PDRP-1002e installation diagram b+ a+ a- b- b+ a+ a- b- b+ a+ a- b- b+ a+ a- b- tb1 tb2 tb3 tb4 batt earth jp 1 supv 2 gen alm2 j1 j2 j9 j3 no dact dact sw1 123456 o n - + no nc c no nc c b+ b- b+ b- b+ a+ a- b- b+ a+ a- b- + - + - +24vnr +24vr tb5 +24vu * * + - 24 vvu rms-regulated 24 vr regulated resettable 24 vnr regulated non-resettable 1234 notification appliance circuits class a (style z) class b (style y) releasing circuits relays trouble alarm contacts contacts 12 34 initiating device circuits class a (style d) class b (style b) abort switch manual release 4xtm or 4xlm or 4xzm 4xtm or 4xlm or 4xzm *jumper ?opt 1? must be cut if a module is installed in this position *jumper ?opt 2? must be cut if a module is installed in this position opt 1 opt 2 micro fail led abort option abort option delay timer cross zone supervisory delay timer ground fault led battery fail led batteries optional ammeter connection transformer ac circuit breaker optional voltmeterconnection 4xrp1002.cdr ground neutral hot
1 the PDRP-1002/PDRP-1002e transmitter module (4xtm - notifier) 8 the PDRP-1002 pn 51135:a 03/11/99 optional boards the PDRP-1002/PDRP-1002e has mounting slots for two option boards. any two of the three option modules may be installed. transmitter module (4xtm - notifier) the transmitter module provides a supervised output for local energy municipal box transmitter (for nfpa 72 auxiliary fire alarm system) and alarm and trouble reverse polarity circuits (for nfpa 72 remote station fire alarm system). also included is a disable switch and disable trouble led. as a jumper option, the alarm reverse polarity circuit will open on trouble if no alarm exists. led interface module (4xlm - notifier) the led interface module supports the rza-4x remote annunciator module. annunciator wiring is supervised for open conditions by this module. the annunciator driver module mounts to the main board, occupying one of the two option connectors. zone relay module (4xzm - notifier) the zone relay module provides form-c contacts for the following: as a jumper option, the first four relays described below can be made silenceable. dip 1=off either zone dip 1=on cross zone if supervisory (dip 2=on) either zone cross zone alarm detected first alarm alarm detected first alarm alarm detected second alarm alarm detected second alarm release 1 release 1 release release release 2 release 2 not used not used 4xtm.cdr 4xlm.cdr 4xzm.cdr
transmitter module (4xtm - notifier) 1 the PDRP-1002/PDRP-1002e the PDRP-1002 pn 51135:a 03/11/99 9 transmitter module (4xtm - notifier) for local energy municipal box service (nfpa 72 auxiliary fire alarm system) supervisory current: 5.0 ma trip current: 0.35 amps. (subtracted from notification appliance power) coil voltage: 3.65 vdc coil resistance: 14.6 ohms maximum allowable wire resistance between panel and trip coil: 3 ohms municipal box wiring can leave the building for remote station service (nfpa 72 remote station fire alarm system): maximum load for each circuit: 10ma reverse polarity output voltage: 24 vdc remote alarm and remote trouble wiring can leave the building led interface module (4xlm - notifier) maximum voltage/current, each output: 27.6v/8ma note: outputs are power limited zone relay module (4xzm - notifier) dry form-c contacts rated: 2.0 amps @ 30vdc (resistive), 0.5 amps @ 30 vac (resistive) remote annunciator remote annunciator (rza-4x - notifier) the remote annunciator mounts on a standard single- gang box, and provides led indication of the same functions as the zone relay module. for example with dip 1=on and dip 2=off:  one zone in alarm (red)  two zones in alarm (red)  releasing circuit 1 (red)  releasing circuit 2 (red)  system trouble (yellow) a local trouble sounder and silence switch are also provided. all led wiring is supervised for open conditions. any open condition will cause the system trouble led to illuminate. note: the remote annunciator requires the use of an led interface module (4xlm). optional meters voltage, current meters (4xmm - notifier) the meter module provides a voltmeter to measure the voltage across the batteries and an ammeter to measure the charging current to the batteries. the meters are provided as an assembly that mounts to the lower left- hand corner of the cabinet. rza4xfr.cdr 0 10 20 30 dc volts 0 5 5 dc amperes voltmter.cdr
1 the PDRP-1002/PDRP-1002e ac power 10 the PDRP-1002 pn 51135:a 03/11/99 specifications ac power for the PDRP-1002: 120 vac, 50/60 hz, 1.2 amps for the PDRP-1002e: 220/240 vac, 50 hz, 0.6 amps wire size: minimum #14 awg with 600v insulation battery (lead acid only) maximum charging circuit: 27.6v, 1.5 amps maximum battery capacity: 15 ah. (batteries larger than 12 ah require notifier #bb-17 or other ul listed external battery cabinet.) initiating device circuits power-limited circuitry operation: class a (style d)/class b (style b) normal operating voltage: 24 vdc (ripple = 1.0v peak-to-peak) alarm current: 15 ma minimum short circuit current: 40 ma maximum maximum detector current in standby: 2 ma (max) per zone maximum loop resistance: 200 ohms end-of-line resistor: 4.7k, 1/2-watt (notifier part # 71252, ul listed) detector loop current is sufficient to ensure operation of one alarmed detector per zone. supervisory current: 5 ma (including end-of-line resistor) notification appliance and releasing circuits power-limited circuitry maximum allowable voltage drop due to wiring: 2 vdc normal operating voltage: 24 vdc total current available to all external devices: 2.25 amps maximum signaling current per circuit: 1.5 amps end-of-line resistor: 4.7k, 1/2-watt (notifier part # 71252, ul listed) alarm and trouble relays dry form-c contacts rated: 2.0 amps @ 30 vdc (resistive), 0.5 amps @ 30 vac (resistive). all relays must be connected to a power limited power supply. four-wire smoke detector power up to 200 ma is available for powering 4-wire smoke detectors. maximum ripple voltage: 1.0 v p/p non-resettable power total dc current available from this output is up to 200 ma (subtracted from 4-wire smoke power). maximum ripple voltage: 1.0 v p/p rms regulated power total dc current available for powering external devices is 0.5 amp (subtracted from 2.25 amps available to notification appliance circuits). maximum ripple voltage: 100 mv p/p note: for device compatibility, refer to device compatibility chart. ac circuit breaker acctbrkr.cdr
rms regulated power 1 the PDRP-1002/PDRP-1002e the PDRP-1002 pn 51135:a 03/11/99 11 figure 2 cabinet dimensions rpcabdim.cdr door = 14.625 in. (371.48 mm) backbox = 14.5 in. (368.3 mm) cabinet = 5.375 in. (136.53 mm) backbox = 4.750 in. (120.65 mm) door = 16.125 in. (409.58 mm) backbox = 16 in. (406.4 mm) 1.5 in (38.1 mm) 16.094 in. (408.79 mm) 14.594 in. (370.69 mm) tr-4xr ruby rd steel 16 ga. optional trim ring tr-4xr
2 system operation rms regulated power 12 the PDRP-1002 pn 51135:a 03/11/99 2 system operation warning:when used for co 2 releasing applications, observe proper precautions as stated in nfpa 12. do not enter the protected space unless physical lockout and other safety procedures are fully completed. do not use software disable functions in the panel as lockout. system status leds alarm, trouble and supervisory leds will flash on and off until the event(s) has been acknowledged (tone or alarm silence), at which point the led will illuminate steadily. ac power green led that illuminates steadily to indicate presence of ac power. system alarm red led that flashes when an alarm occurs. release red led that illuminates steadily when release occurs. supervisory yellow led that flashes upon activation of a supervisory device (such as tamper switch) on output 4 if selected (see ?setting mode of operation? in section 3 of this manual). system trouble yellow led that flashes for any trouble condition, including those associated with option boards. circuit trouble yellow led that flashes for trouble conditions on output circuits (notification and releasing circuits). alarm silenced yellow led that illuminates steadily when the alarm silence switch has been pushed after an alarm. power trouble yellow led that flashes for low or disconnected batteries and earth fault conditions. batt yellow led that illuminates steadily on motherboard when battery is low or not detected (not visible through door). earth yellow led that illuminates steadily on motherboard during a ground fault condition (not visible through door) micro fail yellow led that illuminates on motherboard when watchdog timer detects microprocessor failure (not visible through door) ! batt earth micro fail 4xoper2.cdr
rms regulated power 2 system operation the PDRP-1002 pn 51135:a 03/11/99 13 control switches tone silence acknowledge alarms, troubles and supervisories. the panel has alarm and trouble resound with led flash of new conditions. the flashing trouble led(s) illuminate steadily on tone silence and the piezo sounder silences. a second trouble will resound the piezo. the piezo has three sounds for alarm, trouble, and supervisory. trouble conditions are self-restoring. alarms latch and require reset to clear. alarm silence acknowledge for alarms and supervisories. the alarm silence switch will silence the local piezo, change any flashing alarm leds to steady, and turn off the notification circuits (not the releasing circuits). the ?alarm silenced? led will illuminate. alarm silence is a latching function and requires a reset to clear. alarm activate the alarm activate switch may be used to activate notification appliance circuits. alarm activate also activates the system alarm relay. alarm activate is a latching function. pressing alarm silence silences the notification circuits and system alarm relay and lights the alarm silenced led. pressing reset returns the system to normal. system reset the reset switch breaks power to all initiating circuits, 4-wire smoke power and option boards and will clear any activated output circuits. if any alarms or troubles still exist after reset, they will reactivate the panel. holding reset down will perform a lamp test function and will activate the piezo sounder. zone status leds the alarm and/or trouble led(s) will flash until the event(s) has been acknowledged (tone or alarm silence), at which point the led(s) will illuminate steadily. 4xptl.cdr alarm led trouble led alarm led trouble led abort led abort trouble led manual release manual release trouble led zone 1 zone 2 abort manual release
2 system operation rms regulated power 14 the PDRP-1002 pn 51135:a 03/11/99 supervisory output circuit #4 is used as an input for monitoring supervisory devices such as valve tamper switches (note that sw1 dip switch #2 must be set ?on? -- see section ?setting mode of operation?) by setting switch short circuit on this input (activation of a n.o. contact) will cause the supervisory led to flash. the piezo sounder will generate a unique sound. tone silence will silence the piezo and cause the led to illuminate steadily. supervisory signals latch and require reset to clear. an open circuit will be reported as a circuit trouble. zone disable if a zone has been disabled, an alarm that occurs on that zone will flash the red zone led, but not the piezo or any output circuit. if both power sources are removed from the system, all zones will be re-enabled upon restoration of power. disable status will be lost. the zone disable routine makes use of the four panel switches as follows: 1. press and hold in the tone silence switch. 2. with the tone silence switch held in, press (in sequence) the alarm silence switch, the alarm activate switch, and then the reset switch. 3. the zone 1 alarm led will flash. 4. to disable zone 1, press the reset switch. the zone 1 yellow led will light to show that the zone is disabled. note: the reset switch toggles disable status for the selected zone. 5. to select the next zone, press the alarm silence switch. 6. to select the previous zone, press the alarm activate switch. 7. when disable selections are complete, release the tone silence switch. if any zone has been disabled, the trouble relay will activate and system trouble led will flash. last event recall last event recall allows the user to display the previous panel status. the last event recall uses the four panel switches as follows: 1. press and hold in the tone silence switch. 2. with the tone silence switch held in, press (in sequence) the reset switch, the alarm activate switch, and then the alarm silence switch. 3. last event is displayed. 4. release the tone silence switch to return to normal operation. note: to clear the last event buffer, press reset twice. 4xptl.cdr
ul power limited wiring requirements 3 installation procedure the PDRP-1002 pn 51135:a 03/11/99 15 3 installation procedure general carefully unpack the system and check for shipping damage. mount the cabinet in a clean dry, vibration-free area in which extreme temperatures are not encountered. the location should be readily accessible with sufficient room for easy installation and maintenance. locate the top of the cabinet approximately five feet above the floor with the hinge mounting on the left. determine the number of conductors required for the devices to be employed. pull required conductors into the box through the knockout provided. all wiring should be in accordance with the national and/or local codes for fire alarm systems. ul power limited wiring requirements power limited and non-power limited circuit wiring must remain separated in the cabinet. all power limited circuit wiring must remain at least 0.25 in (6.35 mm) away from any non-power limited circuit wiring. furthermore, all power limited circuit wiring and non-power limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. a typical wiring diagram for the PDRP-1002/ PDRP-1002e is shown below. figure 3 typical wiring diagram for ul power limited requirements 4xtm 4xzm ac power power l i m i te d circuits power limited circuits non-power limited circuits power limited circuit non-power limited circuit notification appliance circuits i n it ia ti n g c i r c u it s r e la y s pc board rp1002pl.cdr
3 installation procedure zones 16 the PDRP-1002 pn 51135:a 03/11/99 initiating device circuits zones wire all alarm initiating devices sequentially for proper supervision. initiating devices include: heat, photoelectric, and ionization type detectors; and waterflow alarm devices. refer to the compatibility chart in appendix b. note:  observe polarity when connecting polarized devices.  all circuits are supervised and power limited.  leave dummy load (provided) on all unused circuits. figure 4 example of an alarm initiating device b+ a+ a- b- b+ a+ a- b- b+ a+ a- b- b+ a+ a- b- tb4 + + + + + + _ _ _ _ _ _ 12 3 4 56 7 8910 11 12 13 14 15 16 aidex.cdr in #1 in #2 in #3 in #4 manual pull station heat detector two-wire smoke detector class b (style b) initiating device circuit 4.7k, 1/2-watt (part # 71252 ul listed) class a (style d) initiating device circuit abort switch 4.7k, 1/2-watt (part # 71252 ul listed) manual release 4.7k, 1/2-watt (part # 71252 ul listed)
zones 3 installation procedure the PDRP-1002 pn 51135:a 03/11/99 17 4-wire smoke detector connections refer to the device compatibility document for suitable 4-wire smoke detectors. figure 5 diagram of connections for a 4-wire smoke detector notes on class a (style d) and class b (style b) field wiring: 1) the power supervision relay coil leads must be connected to the last detector base 24v screw terminals. 2) calculation of the maximum allowable resistance in the 24vdc detector power wiring: r max = (20.6 - v om ) _________________________________________________________________________________________ (n x i s ) + (n a x i a ) + (i r ) where: r max is the maximum resistance of the 24v wires. v om is the minimum operating voltage of the detector or end-of-line relay, whichever is greater, in volts. n is the total number of detectors on the 24v supply loop. i s is the detector current standby. n a is the number of detectors on the 24v power loop which must function at the same time in alarm. i a is the detector current in alarm. i r is the end-of-line relay current. + - 12 3 4 b+ a+ a- b- 12 3 4 tb1 tb4 + + + + - - - - + + + + - - - - a maximum of 200ma is available from the +24vdc 4-wire smoke detector power circuit on tb1 terminals 3 and 4. any power that is drawn from the +24vdc non- resettable power on tb2 terminals 1 and 2 must be subtracted from available 4-wire detector power. (see ?specifications? and ?power? sections.) initiating device circuits 1,2,3, or 4 can be used. class a (style d) wiring can also be employed. rp4wr.cdr ul listed 24 vdc four-wire smoke detectors ul listed 4.7k, 1/2-watt elr listed power supervision relay red black 24 vdc (+) common (-) idc (+) idc (-) 24 vdc (+) common (-) idc (+) idc (-) +24vr in #1 class b initiating device circuit
3 installation procedure notification appliance circuits 18 the PDRP-1002 pn 51135:a 03/11/99 output circuits notification appliance circuits this control panel can provide two class a (style z)/class b (style y) notification appliance circuits and two class b (style y) releasing circuits (see section ?setting mode of operation? for dip switch configuration). each circuit is capable of 1.5 amps of current. total current drawn from all four circuits cannot exceed 2.25 amps. refer to the compatibility chart. circuits are supervised and power-limited. note: wiring must be configured to maintain a minimum voltage of 20.4v on release circuits. calculation of maximum allowable resistance: r max = 20.6v-20.4v ________________________________________________________________________ i s where: r max = maximum allowable resistance of wiring i s = solenoid current figure 6 notification appliance circuits b+ b+ a+ a- b- b+ a+ a- b- nc nc b+ b- b- 345 6 78910111213141516 tb2 + - + - + - + - b+ a+ a- b- b+ b- rpnac.cdr note: output #4 can be configured for releasing or supervisory circuit (see section ?setting mode of oper a configured as a releasing circuit, the circuit will be non-power limited. if configured as a supervisory circuit , will be power limited. all wiring must follow the power limited ?general? section. dummy load all unused notification appliance circuits dummy load all unused releasing circuits 4.7k, 1/4-watt 4.7k, 1/4-watt out #1 out #2 out #3 out #4 see note below polarized horn polarized strobe polarized bell class a (style z) notification appliance circuit class b (style y) notification appliance circuit 4.7k, 1/2-watt (part #71252 ul listed) releasing circuits ul listed & fm approved releasing devices no connection no connection
alarm relay 3 installation procedure the PDRP-1002 pn 51135:a 03/11/99 19 alarm relay one form-c dry alarm contact is provided in the basic panel for controlling supplementary devices. it is rated 2 amps at 30 vdc and 0.5 amps at 30 vac (resistive), and is non-silenceable when an alarm occurs. see below for terminal location. trouble relay one form-c dry trouble contact is provided in the basic panel for controlling supplementary devices. it is rated 2 amps at 30 vdc and 0.5 amps at 30 vac (resistive), and will silence when trouble condition is cleared. see below for terminal location. note: the alarm and trouble form-c dry contact relays must be power limited relays. they must be wired from one of the 24v power limited terminals as shown in the figure below or a comparable ul listed power limited power supply. figure 7 alarm/trouble coils and contacts power caution: several different sources of power can be connected to this panel. disconnect all sources of power before servicing. the panel and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while this unit is energized. figure 8 diagram of power terminals 12 3 4 56 12 3 4 12 tb1 tb2 tb3 rpalmtbl.cdr schematic representation of alarm/trouble coils and contacts. alarm trouble +24vu +24vr +24vnr or or alarm no nc c trouble no nc c ! 1234 12 + - + - + - tb1 tb2 rppwrtrm.cdr this output is not suitable for powering devices requiring filtered dc power. the combined current draws from the resettable and non-resettable outputs cannot exceed 200 ma. rms-regulated power 24 vdc power for inductive- type devices such as door holders can be connected to tb1 terminals 1 (+) and 2(-). 4-wire smoke detector power 24 vdc filtered, resettable power for 4-wire smoke detectors can be obtained from tb1 terminals 3(+) and 4(-). non-resettable power 24 vdc filtered, nonresettable power can be drawn from tb2 terminals 1 (+) and 2(-). +24vu +24vr +24vnr
3 installation procedure ac power 20 the PDRP-1002 pn 51135:a 03/11/99 ac power primary power required for the PDRP-1002 panel is 120 vac, 50/60 hz, 1.2 amps and primary power for the PDRP-1002e is 220/240 vac, 50 hz, 0.6 amps. overcurrent protection for this circuit must comply with article 760 of the national electrical code (nec) and/or local codes. use #14 awg (2.00 mm 2 )or larger wire with 600 volt rating. battery power observe polarity when connecting battery. connect battery cable to j9 on the main board using the plug-in connector provided. see appendix a for calculation of correct battery rating. caution: batteries contain sulfuric acid which can cause severe burns to the skin and eyes, and can destroy fabrics. if contact is made with sulfuric acid, immediately flush skin or eyes with water for 15 minutes and seek immediate medical attention. voltmeter/ammeter to monitor battery voltage and battery charging current, a 4xmm (notifier) is required. to install the power meter module, remove the jumper labeled ?amp? and connect cable assembly p2 to pin connector j2 and cable assembly p3 to pin connector j3 on the main board. secure the 4xmm to the backbox with the two screws provided. on some models, it will be necessary to install the meter bracket with the nuts and bolts provided. figure 9 diagram of the 4xmm voltmeter connected to the main board ! j3 j9 j2 0 10 20 30 dc volts 0 5 5 dc amperes rpmbvm.cdr p2 p3
voltmeter/ammeter 3 installation procedure the PDRP-1002 pn 51135:a 03/11/99 21 optional modules the fire control panel has two module connectors - j5 and j8. three modules are available for the panel and they can be used in any combination, including duplicate modules. the corresponding option jumper must be cut before installation of an optional module. figure 10 optional panel modules j4 j5 j7 j8 note:  optional 4xlm module for an rza-4x annunciator must be installed on j7 and j8 only .  4xtm and 4xzm modules can be installed in either location. *jumper ?opt 2? must be cut if a module is installed in this position micro fail led abort option abort option delay timer cross zone supervisory delay timer ground fault led battery fail led *jumper ?opt 1? must be cut if a module is installed in this position batteries optional ammeter connection transformer optional voltmeterconnection hot neutral ground 4xrp102a.cdr
3 installation procedure installing option modules 22 the PDRP-1002 pn 51135:a 03/11/99 installing option modules insert the two stand-offs (provided) into the holes located on the right-side edge of the main board. carefully align the pins on the main board with j1 and/or j2 on the option board. insert screw through the option board until it is secured on the stand-offs. affix the terminal identification labels provided with the option modules as shown below. figure 11 installing option modules. option board (4xzm shown) (part # 42050) stand-offs) main board 4xstnoff.cdr 4xoptnbd.cdr
transmitter module - 4xtm (notifier) 3 installation procedure the PDRP-1002 pn 51135:a 03/11/99 23 transmitter module - 4xtm (notifier) polarities shown in activated positions. the wiring of this module must follow the requirements as specified in the ?general? section, ? ul power limited wiring requirements. ? push the disconnect switch down to prevent unwanted activation of the municipal box and remote station outputs during testing of the control panel. the disconnect led will remain illuminated while the municipal box is disconnected. the system trouble led will indicate disconnected and/or open circuit conditions on the municipal box. cutting the tbl jumper will allow the alarm reverse polarity circuit to open on trouble, if no alarm exists . note: remote alarm, remote trouble, and municipal box wiring can leave the building. - - - + + + } } } 1 2 3 4 5 6 7 tbl jumper disconnect led disconnect switch remote alarm remote trouble no connection municipal box* * dummy load terminals 6 and 7 (4.7k, 1/4 w resistor) if municipal box is not connected. power limited circuit non-power limited circui 4xtba.cdr
3 installation procedure zone relay module - 4xzm (notifier) 24 the PDRP-1002 pn 51135:a 03/11/99 zone relay module - 4xzm (notifier) non-power limited and power limited wiring must have a minimum distance of 0.25 in. (6.35 mm) wire to wire. if this module is used to drive non-power limited and power limited circuits, please follow the instructions below. 1) skip a set of dry contacts to maintain the 0.25 in (6.35 mm) required space between power limited and non-power limited circuits. the wiring of this module must follow the requirements as specified in the ? general ? section, ? ul power limited wiring requirements .? or 2) if this module is needed to drive power limited and non-power limited relays that are next to each other, refer to the figure below showing a typical connection. relay #1 through #4 will activate with output #1 through #4 and remain latched unless jumper ?latch? is cut. 1 no 2 nc 3 c 4 no 5 nc 6 c 7 no 8 nc 9 c 10 no 11 nc 12 c 13 no 14 nc 15 c 16 no 17 nc 18 c relay #1 relay #2 relay #3 relay #4 alarm trouble cut jumper for non-latching (silenceable) relay operation. use disable switch to disconnect the relays. 4xzma.cdr note: refer to the protected premises unit label, located on the door of the control panel, to indicate if any dry contacts are to be used as non-power limited dry contacts. 4xzmptl.cdr relay #1 relay #2 relay #3 relay #4 no nc c no nc c no nc c no nc c power limited circuit power limited circuit no connection non-power limited circuit non-power limited circuit
led interface module - 4xlm (notifier) 3 installation procedure the PDRP-1002 pn 51135:a 03/11/99 25 led interface module - 4xlm (notifier) the wiring of this module must follow the requirements as specified in section? ul power limited wiring requirements .? figure 12 led interface module - 4xlm connect to corresponding terminals of rza-4x remote annunciator. note: make wiring connections with system power off. maximum wire impedance is 50 ohms per wiring connection. front view side view single-gang box 1 +24v 2 out#1 3 out#2 4 out#3 5 out#4 6 system trouble 7 sound 8 resound rza4xfr.cdr rza4xbx.cdr 4xlma.cdr
3 installation procedure dip switch 26 the PDRP-1002 pn 51135:a 03/11/99 setting mode of operation dip switch the dip switch is located at the bottom of the PDRP-1002/PDRP-1002e main board. to set a switch to the ?on? position, slide the switch up until it stops. the flush- surface switches are designed to prevent accidentally changing a switch setting and may therefore require use of a pen or screwdriver to set them. note: the reset key must be depressed after any switch configuration has been made. cross zone select the desired mode of operation and set sw1 dip switch 1. note: outputs 1 and 2 refer to notification appliance circuits. output 3 refers to a releasing circuit. output 4 is determined by setting switch 2. zones 1 and 2 refer to initiating device circuits. switch 1 off on output 1 is activated by an alarm on either zone 1 or zone 2 . output 1 (pre-discharge alarm) is activated by the first alarmed zone in the system. initiation of an alarm on the other zone will shut this output off. output 2 is activated by an alarm on either zone 1 or zone 2 . output 2 will pulse at 60 ppm while timer is running or frozen by abort. output 2 will sound steadily upon release (time out). output 2 is activated when alarms occur on both zone 1 and zone 2 . output 2 will pulse at 60 ppm while timer is running or frozen by abort. output 2 will sound steadily upon release (time out). outputs 3 and 4 will be activated when the timer expires (provided that output 4 is functioning as a releasing circuit - set via dip switch 2). the timer will start whenever an alarm occurs on either zone 1 or zone 2 . the timer will start when alarms occur on both zone 1 and zone 2 . 1 2 34 5 6 o n 1 2 3456 o n battery fail led ground fault led micro fail led switch 3: delay timer switch 4: delay timer switch 5: abort option switch 6: abort option switch 1: cross zone switch 2: supervisory 4xrpdips.cdr dip switches
output 4 supervisory/releasing service 3 installation procedure the PDRP-1002 pn 51135:a 03/11/99 27 output 4 supervisory/releasing service set the function of output 4 via sw1 dip switch 2. timer select the desired timer setting and set sw1 dip switches 3 and 4 per the appropriate column. abort function select the desired abort functions and set sw1 dip switches 5 and 6 per the appropriate column. note: abort timer will not operate when timer is set for ?no delay?. switch 2 off on output 4 will function as a solenoid releasing circuit. this circuit will be a non-power limited circuit in this mode. output 4 will function as a supervisory input circuit. a short condition on this circuit will illuminate the supervisory led and sound the supervisory tone on the piezo. an open condition generates a circuit trouble condition. this circuit will function as a power limited circuit in this mode. no delay* 10 seconds 20 seconds 30 seconds switch 3 off off on on switch 4 off on off on *abort switch is inoperative when no delay is selected. switch 1 off off on on switch 2 off on off on standard ul-type delay timer which continues to count down upon abort, and stops and holds at 10 seconds until release of the abort switch. upon release of the abort switch, the timer resumes the countdown at 10 seconds. iri-type delay timer which functions the same as the ul-type timer with the exception that the abort will function only if pressed and held before 2nd zone goes into alarm. nyc-type delay timer. pressing abort, once an alarm exists, changes timer value to the time selected via dip switches 3 and 4 plus 90 seconds. the timer will not start as long as the abort switch is held. system reset restores timer to original times selected via dip switches 3 and 4. successive aborts will add 90 seconds to selected timer value. local jurisdiction delay timer. once the timer has started, pressing abort restores timer to its full time as set on dip switches 3 and 4. the timer will not start as long as abort is held. release of the abort switch continues the countdown, whereas pressing abort again will restore the timer to its full value. these modes are the only ones that comply with ul standard 864
appendix a: power calculations standby battery requirements 28 the PDRP-1002 pn 51135:a 03/11/99 appendix a: power calculations standby battery requirements the standby battery current figure obtained in the following table (table 1) represents the amount of current that must be supplied by the secondary power source (batteries) to sustain control panel operation for one hour. table 1 standby battery requirements note: the control panel will support the installation of one or two optional modules, including two of the same type of module. basic control panel control panel with ac power off, system trouble led and audible trouble sounder on. 88 ma if using a 4xzm zone relay module 1 [ ] x 8 ma = i f using a 4xtm transmitter module, add 11 ma if using the reverse polarity alarm output, add 5 ma if using the reverse polarity trouble output, add 5 ma if using a 4xlm/rza-4x driver/annunciator combination: 1 [ ] x 19 ma = if using a 4xmm meter module, add 1 ma if using the notifire 911ac dact, add 30 ma a. two-wire detector heads b. four-wire detector heads c. end of line relays d. add lines a, b, & c for place subtotal here add last column for standby battery current : and continue to next table (table 2) device current (see appendix b for data) number in use to t a l current x = x = x 25.0 ma =
ampere-hour calculations appendix a: power calculations the PDRP-1002 pn 51135:a 03/11/99 29 ampere-hour calculations table 2 ampere-hour calculations select a battery with an equal or greater amp/hour rating than the figure obtained in table 2. batteries must be lead-acid type. ps-1270 12 volt, 7 amp/hour (two required) ps-12120 12-volt, 12 amp/hour (two required) notes: 1. alarm amp-hours assumes a maximum system draw of 3 amps in alarm for 5 minutes (0.25 amp/hour) or for 10 minutes (0.5 amp/hour) 2. nfpa 72 central station and local and proprietary fire alarm systems require 24 hours of standby. 3. nfpa 72 auxiliary and remote station fire alarm systems require 60 hours of standby. 4. factory mutual systems require 90 hours of standby. 5. the battery charger in this panel will charge a maximum of 15 amp/hours of batteries within 48 hours (7 amp/hour minimum). batteries larger than 12 amp/ hour will require a ul listed battery cabinet (e.g. notifier bb-17). standby battery current convert the total from table 1 to amps and enter here standbytime 24, 60, or 90 hours amps x hours = standby amp/hours alarm amp/hours to t a l a m p / hours needed enter 0.25 for 5 minutes in alarm or 0.5 for 10 minutes in alarm + add standby and alarm amp/hours =
appendix b: device compatibility fm-approved releasing devices 30 the PDRP-1002 pn 51135:a 03/11/99 appendix b: device compatibility table 3 ul listed four-wire smoke detectors fm-approved releasing devices (system sensor?s PDRP-1002/PDRP-1002e) solenoid group [a] skinner solenoid valve model lv2lbx25, 24 vdc, 11 watts, 458 ma, 1/2 in. nps, 5/ 8 in. orifice. solenoid group [b] these valves are interchangeable . asco solenoid valve model t8210a107, 24 vdc, 16.8 watts, 700 ma, 1/2 in. nps, 5/8 in. orifice. asco solenoid valve model r8210a107, 24 vdc, 16.8 watts, 700 ma, 1/2 in. nps, 5/8 in. orifice. asco solenoid valve model 8210a107, 24 vdc, 16.8 watts, 700 ma, 1/2 in. nps, 5/ smoke detector/base detector type max standby current (ma) max alarm current (ma) system sensor 2424 photoelectric 0.10 41 system sensor 2424th photoelectric 0.10 41 system sensor 2451 photoelectric 0.10 39 system sensor 2451th (with/b402b base) photoelectric 0.10 39 system sensor 1424 ionization 0.10 41 system sensor 1451 (w/b402b base) ionization 0.10 39 system sensor 2412 photoelectric 0.12 77 system sensor 2412at photoelectric 0.12 58 system sensor 2412th photoelectric 0.12 77 system sensor 2312/24tb photoelectric 0.12 50 system sensor b112lp base see note 39 system sensor b114lp base see note 75 system sensor b404b base see note see note system sensor 6424 projected beam 10 28.4 system sensor dh400acdci ionization duct 25 95 system sensor dh400acdcp photoelectric duct 25 95 system sensor 1112/24 ionization 0.05 50 system sensor 2112/24 photoelectric 0.05 50 system sensor 2112/24b photoelectric 0.05 65 system sensor 2112/24t photoelectric w/135 thermal 0.05 50 system sensor 2112/24tsrb photoelectric w/135 thermal supervisory relay 15 45 note: contact manufacturer for currents.
fm-approved releasing devices appendix b: device compatibility the PDRP-1002 pn 51135:a 03/11/99 31 8 in. orifice. solenoid group [c] star sprinkler corp. solenoid p/n 5550, 24 vdc, part of model d deluge valve. kidde-fenwal electric control head p/n 890181; 24v, 2.0 amps kidde-fenwal electric control head p/n 899175; 24v, 2.0 amps kidde-fenwal electric control head stackable (xp) p/n 48650001; 24v, 0.2 amps kidde-fenwal electric and cable op control head (xp) p/n 897494; 24v, 1.5 amps, 33 watts refer to the fm approval guide for automatic water control valves which are compatible with solenoids listed above. table 4 24 vdc door holders table 5 ul listed 24 vdc relays model type current (ma) fm980-24 floor mount, single 68 fm996-24 wall mount surface wiring 68 fm998-24 wall mount concealed wiring 68 vendor model current(ma) system sensor a77-716b 20 air products & controls, ltd mr-101/c mr-201/c 15 35
appendix b: device compatibility fm-approved releasing devices 32 the PDRP-1002 pn 51135:a 03/11/99 system sensor rated vo l t a g e 2 fwr dc filtered dc system sensor ma-12/24d electronic sounder 24vdc 73 46 system sensor ss24 strobe 24vdc note 5 30 system sensor ss24lo strobe 24vdc 45 25 system sensor ss24loc ceiling strobe (ss24lobc - beige) 24vdc 45 25 system sensor ss24m strobe 24vdc 125 75 system sensor ss24mc ceiling strobe 24vdc 125 75 system sensor mass24d electronic sounder/strobe 24vdc 118 71 system sensor mass24lo electronic sounder/strobe 24vdc 118 71 system sensor mass24loc electronic ceiling sounder/strobe 24vdc 118 71 system sensor mass24lola electronic sounder/strobe with fuego lens 24vdc 118 71 system sensor mass24m electronic sounder/strobe 24vdc 198 121 system sensor mass24mc electronic ceiling sounder/strobe 24vdc 198 121 system sensor pa400r sounder 24vdc note 5 15 system sensor ps24lo add-on strobe 24vdc 45 25 system sensor ss2415ada signaling strobe 24vdc 90 75 system sensor ss2475ada signaling strobe 24vdc 200 170 system sensor ss24110ada signaling strobe 24vdc 245 210 system sensor ss241575ada signaling strobe 24 vdc 120 93 system sensor ss2415adas signaling strobe with synch. circuit 24 vdc 125 106 system sensor ss241575adas signaling strobe with synch. circuit 24 vdc 180 115 system sensor mass2415ada sounder/signaling strobe 24vdc 163 121 system sensor mass2475ada sounder/signaling strobe 24vdc 273 216 system sensor mass24110ada sounder/signaling strobe 24vdc 318 256 system sensor mass241575ada sounder/signaling strobe 24 vdc 193 139 system sensor mass2415adas sounder/signaling strobe w/ synch. ckt. 24 vdc 163 121 system sensor mass241575adas sounder/signaling strobe w/ synch. ckt. 24 vdc 193 139 system sensor ps2415ada mini-sounder/strobe 24vdc 110 90 system sensor ps2475ada mini-sounder/strobe 24vdc 135 108 system sensor ps241575ada mini-sounder/strobe 24vdc 135 108 system sensor ps24110ada mini-sounder/strobe 24vdc 240 225 system sensor sp1r2415ada speaker/signaling strobe 24vdc 90 75 system sensor sp1r2475ada speaker/signaling strobe 24vdc 200 170 system sensor sp1r24110ada speaker/signaling strobe 24vdc 245 210
fm-approved releasing devices appendix b: device compatibility the PDRP-1002 pn 51135:a 03/11/99 33 system sensor sp1r241575ada speaker/signaling strobe 24 vdc 120 93 system sensor v4r2415ada speaker/signaling strobe 24vdc 90 75 system sensor v4r2475ada speaker/signaling strobe 24vdc 200 170 system sensor v4r24110ada speaker/signaling strobe 24vdc 245 210 system sensor v4r241575ada speaker/signaling strobe 24 vdc 120 93 system sensor sp100w24loc ceiling speaker/strobe, 8" round grille 24vdc 45 25 system sensor sp101r24lo speaker/strobe, 5" square grille 24vdc 45 25 system sensor sp101r24m speaker/strobe, 5" square grille 24vdc 125 75 system sensor sp100w24mc ceiling speaker/strobe, 8" round grille 24vdc 125 75 system sensor ma12/24eh multi alert horn with mechanical tone 12vdc/ 24vdc 20/64 38/43 system sensor maeh24lo multi alert horn with mechanical tone/strobe 24vdc 109 68 system sensor maeh24loc multi alert horn with mechanical tone/strobe 24vdc 109 68 system sensor maeh24lola multi alert horn with mechanical tone/strobe 24vdc 153 96 system sensor maeh24m multi alert horn with mechanical tone/strobe 24vdc 189 118 system sensor maeh24mc multi alert horn with mechanical tone/strobe 24vdc 189 118 system sensor maeh1215ada multi alert horn with mechanical tone/strobe 12vdc 240 191 system sensor maeh121575ada multi alert horn with mechanical tone/strobe 12vdc 310 246 system sensor maeh2415ada multi alert horn with mechanical tone/strobe 24vdc 278 216 system sensor maeh2475ada multi alert horn with mechanical tone/strobe 24vdc 273 216 system sensor maeh241575ada multi alert horn with mechanical tone/strobe 24vdc 343 271 system sensor maeh24110ada multi alert horn with mechanical tone/strobe 24vdc 318 256 system sensor maeh2415adas multi alert horn with mechanical tone/strobe 24vdc 198 152 system sensor maeh241575adas multi alert horn with mechanical tone/strobe 24vdc 253 241 system sensor h12 spectralert horn 12vdc 25 14 system sensor h42 spectralert horn3 24vdc 42 37 system sensor s1215 spectralert strobe 12vdc 159 133 system sensor s121575 spectralert strobe 12vdc 182 168 system sensor s2415 spectralert strobe3 24vdc 142 83 system sensor s241575 spectralert strobe3 24vdc 132 76 system sensor s2475 spectralert strobe3 24vdc 170 145 system sensor s24110 spectralert strobe3 24vdc 220 169 system sensor p1215 spectralert horn/strobe 12vdc 173 144 system sensor p121575 spectralert horn/strobe 12vdc 196 179 system sensor p2415 spectralert horn/strobe3 24vdc 165 94 system sensor p241575 spectralert horn/strobe3 24vdc 177 111
appendix b: device compatibility fm-approved releasing devices 34 the PDRP-1002 pn 51135:a 03/11/99 table 6 ul listed notification appliances system sensor p2475 spectralert horn/strobe3 24vdc 215 180 system sensor p24110 spectralert strobe3 24vdc 265 214 system sensor rp1215adaaretrofit strobe plate 12vdc 200 170 system sensor rp121575adaaretrofit strobe plate 12vdc 240 255 system sensor rp2415adaaretrofit strobe plate 24vdc 90 75 system sensor rp241575adaaretrofit strobe plate 24vdc 120 93 system sensor rp2475adaaretrofit strobe plate 24vdc 200 170 system sensor rp24110adaaretrofit strobe plate 24vdc 245 210 system sensor h24 spectralert 24vdc 42 37 system sensor s2415 spectralertstrobe3 24vdc 142 83 system sensor s241575 spectralert strobe3 24vdc 132 76 system sensor s2475 spectralert strobe3 24vdc 170 145 system sensor s24110 spectralert strobe3 24vdc 220 169 system sensor s2415 spectralert horn/strobe3 24vdc 165 94 system sensor s241575 spectralert horn/strobe3 24vdc 177 111 system sensor s2475 spectralert horn/strobe3 24vdc 215 180 system sensor p24110 spectralert horn/strobe3 24vdc 265 214 system sensor s2415 spectralertstrobe3 24vdc 142 83 system sensor s241575 spectralert strobe3 24vdc 132 76 note: 1) control panels suppling special application (fwr, filtered) power must use the notification appliances, relays or door holders listed in this table. 2) all currents are in millamperes and worst case average. 3) nominal operating voltage. 4) refer to installation instructions for more information. 5) contact manufacturer for currents.
fm-approved releasing devices appendix b: device compatibility the PDRP-1002 pn 51135:a 03/11/99 35 table 7 ul listed, compatible two-wire smoke detectors for notifier control panels number of detectors per zone model det. id detector type base model base id standby current (ua) PDRP-1002/ PDRP-1002e system sensor 1400 a ionization n/a n/a 100 20 system sensor 1451 a ionization b401b / b406b a 120 15 / 1 system sensor 1851dh a ionization dh1851dc a 120 15 system sensor 2400 a photoelectric n/a n/a 120 15 system sensor 2400ait a photo / isolated thermal / horn n/a n/a 120 1 system sensor 2400at a photo / thermal / horn n/a n/a 120 1 system sensor 2400th a photo / thermal n/a n/a 120 15 system sensor 2451 a photoelectric b401b / b406b a 120 15 / 1 system sensor 2451th a photo / thermal b401b / b406b a 120 15 / 1 system sensor 2851dh a photoelectric dh2851dc a 120 15 system sensor 1451dh a ionization dh-400 a 120 15 system sensor 2451 a photoelectric dh-400 a 120 15 system sensor 2300t a photo / thermal n/a n/a 120 15 system sensor 1800 a ionization n/a n/a 100 n/a system sensor 1851b a ionization b101b a 120 n/a system sensor 1851b a ionization b107b a 120 n/a system sensor 2800 a photoelectric n/a n/a 120 n/a system sensor 2800th a photo / thermal n/a n/a 120 n/a system sensor 2851b a photoelectric b101b a 120 n/a system sensor 2851b a photoelectric b107b a 120 n/a system sensor 2851bth a photo / thermal b101b a 120 n/a system sensor 2851bth a photo / thermal b107b a 120 n/a system sensor 1151 a ionnization b401 / b110lp / b116lp a 120 15 / 15 / 1 system sensor 2151 a photoelectric b401 / b110lp / b116lp a 120 15 / 15 / 1
appendix c: nfpa standard-specific requirements fm-approved releasing devices 36 the PDRP-1002 pn 51135:a 03/11/99 appendix c: nfpa standard-specific requirements the PDRP-1002/PDRP-1002e has been designed for use in commercial, industrial, and institutional applications and meets the requirements for service under the national fire protection association (nfpa) standards outlined in this appendix. the minimum system components required for compliance with the appropriate nfpa standards are listed below. PDRP-1002/PDRP-1002e control panel containing the main control board, cabinet (backbox and door), main supply transformer and power supply. batteries (refer to appendix a for standby power requirements). initiating devices - connected to one of the control panel?s initiating device circuits. notification appliances - connected to one of the control panel?s notification appliance circuits. releasing devices - connected on one of the control panel?s releasing circuits. the following additional equipment is needed for compliance with the nfpa standards listed below. nfpa 72 signaling systems for central station service (protected premises unit) notifire 911ac dact* - for connection to a compatible listed central station dacr or protected premises receiving unit. this unit must be installed as outlined in figure 13. nfpa 72 auxiliary fire alarm system 4xtm transmitter module for connection to a compatible listed local energy municipal box. this unit must be installed as outlined in figure 15. nfpa 72 remote station fire alarm system 4xtm transmitter module for connection to firelite rs82-9 remote station receiver. see figure 16 for installation instructions. or notifire 911ac dact* - for connection to a compatible listed remote station dacr. this unit must be installed as outlined in figure 13. *applications which require the notifire 911ac are not fm approved .
nfpa 72 signaling systems for central station service appendix c: nfpa standard-specific requirements the PDRP-1002 pn 51135:a 03/11/99 37 nfpa 72 signaling systems for central station service (protected premises unit) and remote station fire alarm system (protected premises unit) notifire 911ac dact* - for connection to a central station receiver or protected premises receiving unit. this unit must be installed as illustrated below. for additional information on the 911ac, refer to document 74-06200-005. all connections between the facp and 911ac must be in conduit, less than 20 ft (609.6cm) in length in the same room. if the notifire 911ac is not mounted in the PDRP-1002/PDRP-1002e backbox all connections must be in conduit, less than 20 ft. (609.6 cm) in length in the same room. *this application using the notifire 911ac is not fm approved. note: for 911ac  the maximum standby load shall be 125 ma.  the standby by battery requirement: 24vdc, 7amp-hour-max.  the PDRP-1002/PDRP-1002e is not suitable for transmission of a supervisory signal to the dact. figure 13 nfpa 72 signaling systems for central station service 1 2 4 6 7 8 9 10 11 12 3 5 1 2 5 6 7 8 9 10 12 13 14 15 16 17 3 4 11 1 2vac, 20va, 60hz or +2 4vdc 1 2vac, 20va, 60hz or -2 4vdc (refer to manual) battery - battery + ini t iat in g a1 - ini t iat in g a2 - ini t iat in g b1 + ini t iat in g b2 + s u pe rv is o r y h i s u pe rv is o r y l o trouble relay nc trouble relay com trouble relay no alarm relay nc alarm relay com alarm relay no digital ala rm co mm unicator transm itter listed for ce ntral station o r r em ote station s ervic e. s lide cov er back to acces s progr am m ing ja c k a nd relay s primary rj31x te l c o j a c k a lte rn ate r j31x te l c o j a c k - 12 vd c sea led r e c h a rg e ab le + b a tt e ry ps1270 12volt 7ah battery + - note on std dact: place jumper over pins 2 and 3, marked dact, when employing a dact. this directs the control panel to transmit all trouble conditions except ac loss. std dact to central station alarm jp-1 motherboard 911ac alarm normally open contacts tb3-1 6 and 7 tb3-3 8 and 9 trouble normally open contacts tb3-4 10 tb3-6 11 note: the PDRP-1002/ PDRP-1002e is not suitable for transmission of a supervisory signal to the dact rp911ac.cd to ac power
appendix c: nfpa standard-specific requirements nfpa 72 signaling systems for central station service 38 the PDRP-1002 pn 51135:a 03/11/99 using the ms-5012 as a dact 1) reference the ms-5012 manual for additional information. 2) program the ms-5012 for slave applications. 3) the PDRP-1002/PDRP-1002e is not suitable for transmission of a supervisory signal to the dact. figure 14 using the ms-5012 as a dact tb2 tb3 alarm ac power trouble supervisory 1 23 4 5 6 7 8 9 f e d c a ob 1st event enter store j2 j3 tb3 ac wiring for dact/facp must be connected to the same circuit. motherboard ms-5012 alarm tb3-1 tb2-2 tb3-3 tb2-1 trouble tb3-4 tb2-4 tb3-6 tb2-3 red black ye l lo w ye l lo w black white green ground neutral hot 120 vac 12vdc battery 2-7ah trouble alarm primary phone line secondary phone line modular cable p/n mcbl-6 ms5012x2.cdr ms-5012 PDRP-1002/PDRP-1002e 1 2 3 4 5 6
nfpa 72 auxiliary fire alarm system appendix c: nfpa standard-specific requirements the PDRP-1002 pn 51135:a 03/11/99 39 nfpa 72 auxiliary fire alarm system all connections are power limited and supervised. this application is not suitable for separate transmission of sprinkler supervisory or trouble conditions. note: maximum loop resistance allowed for wiring from control panel to municipal box is 3 ohms. figure 15 nfpa 72 auxiliary fire alarm system 4xtb fire gamewell model m34-56 local energy municipal box + municipal box circuit - 4xtm (notifier) transmitter module (activated polarities shown) + - 6 7 auxpross.cdr
appendix c: nfpa standard-specific requirements nfpa 72 remote station fire alarm system 40 the PDRP-1002 pn 51135:a 03/11/99 nfpa 72 remote station fire alarm system intended for connection to a polarity reversal circuit of a remote station receiving unit having compatible ratings. all connections are power limited and supervised with the exception of the reverse polarity loop. supervision of the loop is the responsibility of the receiver. figure 16 nfpa 72 remote station fire alarm system 1 1 1 1 1 1 1 1 1 1 5 1 1 1 3 7 2 2 2 2 2 2 2 2 2 2 2 2 2 4 8 6 1 12 14 10 13 9 11 -- -- k -- -- -- k k | | | | | | | | | | k + - - + h 4xtm (notifier) transmitter module (activated polarities shown) remote alarm remote trouble 1 2 3 4 + + - - firelite rs82-9 remote station receiver ul listed rempross.cdr power transformer recommended types: elpower ep 1250c power sonic ps 1245 power sonic ps 1260 power sonic ps 1265 yuasa npg-12 or equivalent maximum battery size 6.0 x 2.6 x 4.1 in. (15.24 x 6.6 x10.41 alarm signal input 3 } alarm signal input 4 } alarm signal input 5 } alarm signal input 6 } alarm signal input 7 } alarm signal input 8 } alarm signal input 9 } optional zone card (rsz) circuit side remote station master board (rsm-9) control card (rsc) circuit side filter cap signaling relay for bells and dry contacts dry supplementary contacts, rated 3a, 120 vac resistive 3a, 30 vdc resistive n.c.2 n.o.2 pole 2 n.c.1 n.o.1 pole 1 a.c. ckt breaker 120 vac 1.2 amps press to reset battery ckt fuse 8 ag 5 a 125 v grounding terminal } 120 vac 1.2 a 50-60 hz input n/c batt conn bell or horn 10 k elr optional zone card (rsz) circuit side optional zone card (rsz) circuit side optional zone card (rsz) circuit side optional zone card (rsz) circuit side optional zone card (rsz) circuit side optional zone card (rsz) circuit side optional zone card (rsz) circuit side zone card(rsz) circuit side
nfpa 72 remote station fire alarm system appendix c: nfpa standard-specific requirements the PDRP-1002 pn 51135:a 03/11/99 41 troubleshooting table table 8 trouble shooting table symptom problem solution ac power led on system trouble led on circuit trouble led on notification appliance circuit trouble 1. check tb2 for proper connections. (tb3 for 4xb panels) 2. remove all field wiring and install dummy elr at output circuit. check for supervisory voltage across it. (normal -2.3 v). if problem persists, replace circuit board. 3. removed dummy elr, reconnect field wiring and measure voltage across output; (trouble -5v, short ov). 4. check for elr at last device. 5. check field wiring. any of the right column yellow leds flashing initiating zone open circuit trouble 1. check tb4 for proper connections. 2. remove field wiring for zone in trouble and install dummy elr (4.7k for 24v; 2.2k for 12v). if problem persists, replace circuit board. 3. check for elr at last device. 4. check field wiring. any of the right column yellow leds steady on zone disable check installation manual. power trouble led on battery trouble batt yellow led on missing or disconnected check battery connections low or damage battery 1. remove batteries, check voltage across charger output (17 to 19v for 24v; 8-10v for 12v), otherwise replace circuit board. 2. reconnect batteries, measure battery voltage at battery terminals. if voltage is less than 85% of rated voltage, allow them to charge for 48 hours. 3. if problem persists, replace batteries. ground fault trouble earth yellow led on 1. remove field wiring from main panel and optional module(s) (if installed). install dummy elr (4.7k for 24v; 2.2k for 12v). 2. remove both battery leads. 3. if trouble clears, connect one circuit at a time to pinpoint the problem. 4. if trouble doesn?t clear, replace circuit board. yellow led on 4xtm on 4xtm 1. move municipal box disconnect switch sw1 up opt1, opt2 jumper cut install optional module(s) or replace jumper if module(s) is not used. municipal box open circuit 1. install dummy load if municipal box option isn?t used. 2. check municipal box wiring. any of the right column red leds on short on initiating circuit wiring remove field wiring and install elr. if trouble clears, look for faulty or incorrectly wired devices. disconnecting municipal box switch on 4xtm does not create a trouble jumper for optional modules isn?t cut. cut associated jumper opt1 or opt2. 4xzm: associated led does not activate for alarm, trouble or supervisory conditions optional module trouble 1. make sure module is properly installed. 2. move disable switch sw1 on 4xzm to the left. rza-4x piezo doesn?t sound for alarm, trouble or supervisory conditions 4xlm 1. make sure that 4xlm module is installed on j7 and j8. 2. check field wiring. micro fail yellow led on microprocessor damaged. replace circuit board. all rza-4x leds stay on power wasn?t removed prior to installation. hit system reset. ac power led off system trouble led on loss of main power check incoming power (tb5). (tb1 for 4xb panels) damaged circuit breaker replace circuit board. micro fail yellow led on microprocessor damaged replace circuit board.
appendix c: nfpa standard-specific requirements nfpa 72 remote station fire alarm system 42 the PDRP-1002 pn 51135:a 03/11/99 notes
nfpa 72 remote station fire alarm system appendix c: nfpa standard-specific requirements the PDRP-1002 pn 51135:a 03/11/99 43 notes
appendix c: nfpa standard-specific requirements nfpa 72 remote station fire alarm system 44 the PDRP-1002 pn 51135:a 03/11/99 system sensor 3825 ohio avenue, st. charles, il 60174 1-800-sensor2 fax: 630-377-6495 limited warranty system sensor ? warrants its products to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. products are date stamped at time of manufacture. the sole and exclusive obligation of system sensor ? is to repair or replace, at is option, free of charge for parts and labor, any part which is defective in materials or workmanship under normal use and service. for products not under system sensor ? manufacturing date-stamp control, the warranty is eighteen (18) months from date of original purchase by system sensor ? distributor unless the installation instructions or catalog sets forth a shorter period, in which case the shorter period shall apply. this warranty is void if the product is altered, repaired or serviced by anyone other than system sensor ? or its authorized distributors or if there is a failure to maintain the products and systems in which they operate in proper and workable manner. in case of defect, phone system sensor ? repair department, ra #_____________, 3825 ohio avenue, st. charles, il 60174. please include a note describing the malfunction and suspected cause of failure. this writing constitutes the only warranty made by system sensor ? with respect to its products. system sensor ? does not represent that its products will prevent any loss by fire or otherwise, or that its products will in all cases provide the protection for which they are installed or intended. buyer acknowledges that system sensor ? is not an insurer and assumes no risk for loss or damages or the cost of any inconve- nience, transportation, damage, misuse, abuse, accident or similar incident. system sensor ? gives no warranty, expressed or implied, of merchantability, fitness for any particular purpose, or otherwise which extend beyond the description on the face hereof. under no circumstances shall system sensor ? be liable for any loss of or damage to property, direct, incidental or consequential, arising out of the use of, or inability to use system sensor ? products. furthermore, system sensor ? shall not be liable for any personal injury or death which may arise in the course of, or as a result of, personal, commercial or industrial use of its products. this warranty replaces all previous warranties and is the only warranty made by system sensor ? . no increase or alteration, written or verbal, of the obligation of this warranty is authorized.


▲Up To Search▲   

 
Price & Availability of PDRP-1002

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X